EasyManuals Logo

Hitachi 670 Series Application Guide

Hitachi 670 Series
102 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #48 background imageLoading...
Page #48 background image
Table 5: Relevant settings
Setting Value Remark
IdMin 0.20 20 % of IBase = 1000 A
Must be set above the maximum possible charging current (in this
example set to approximately 2 x of that value).
EndSection1 1.00 100 % of IBase = 1000 A
EndSection2 3.00 300 % of IBase = 1000 A
SlopeSection2 0.50 Slope = 50 %
SlopeSection3 1.00 Slope = 100 %
IdMinHigh 1.00 100 % of IBase = 1000 A
tIdMinHigh 1000 Interval of initial decreased sensitivity in ms.
IdUnre 3.00 300 % of IBase = 1000 A
Maximum through fault current calculated based on:
220
2.45
3 (4.84 58.64)
ThroughI kA

IECEQUATION15178 V1 EN-US
1.2 1.2 2.45
2.94
1
Through
dUnre
Base
I kA
I kA
I kA

IECEQUATION15179 V1 EN-US
I2/I1Ratio 0.10 Ratio = 10 %
The value can be set this low because the 2
nd
harmonic block is
ignored if an internal fault is detected.
I5/I1Ratio 0.10 Ratio = 10 %
The value can be set this low because the 5
th
harmonic block is ignored
if an internal fault is detected and no tap transformer exists in the
protected zone.
CCCOpMode 1 The exact method with currents and voltages is used. Line
capacitances must be specified.
VTOnLineGrp1 0 VT is placed on the bus.
VTOnLineGrp2 0 VT is placed on the bus.
C0 7.751e-9 x 200 Total zero sequence capacitance of 220kV on a 200 km power line.
C1 12.74e-9 x 200 Total positive sequence capacitance of 220kV on a 200 km power line.
NoOfLineEnds 2 Number of physical line ends in the protected zone (setting used by
charging current compensation).
NoOfCTSetsGrp1 1 Number of three-phase CT groups at first line end, the currents of which
are connected to input group 1 (setting used by charging current
compensation).
NoOfCTSetsGrp2 1 Number of three-phase CT groups at second line end, the currents of
which are connected to input group 2 (setting used by charging current
compensation).
IBase 1000 Nominal current of the protected power line.
Table continues on next page
Section 4 1MRK505382-UEN Rev. K
Analog and binary signal transfer for line differential protection
42 Communication set-up, 670/650 series
Application Guide
© 2017 - 2023 Hitachi Energy. All rights reserved

Table of Contents

Other manuals for Hitachi 670 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Hitachi 670 Series and is the answer not in the manual?

Hitachi 670 Series Specifications

General IconGeneral
BrandHitachi
Model670 Series
CategoryControl Unit
LanguageEnglish

Related product manuals