5 Optional functions
Optional functions through Remote control
SMGB0137 rev.0 - 05/2021
107
5
5.2 Optional functions through Remote control
The next list refers to the optional functions available to indoor units from the remote control switch. Note that not all
remote control switch have access to all the optional functions. Check the remote control switch technical documentation
for detailed information.
5.2.1 List of optional remote control functions (PC-ARFP1E)
Element Optional function
Individual
setting
Settings
Setting conditions Description
b1
Heating temperature
compensation
Models:
RCI-FSR
RCIM-FSRE
RCD-FSR
RPC-FSR
RPI(L/H)-FSRE
RPI-FSN3E(P)E(-f)
RPK-FSR(H)M
O
00
Normal (factory setting)
(Setting Temperature + 4 ºC)
This function is used to adjust
the temperature di󰀨erence 
between the temperature read
by the inlet sensor and the real
room temperature.
This is useful when the inlet air
thermistor is not placed inside
the indoor unit or due to uneven
heat load.
? NOTE
The “02”, “03”, “04” settings
may not be available
depending on the type of
indoor unit.
This setting shall be
performed separately for
each indoor unit, even in
case that multiple indoor
units are connected to one
remote controller.
01
No compensation
(Setting Temperature)
02
Setting Temperature + 2 ºC
03
Setting Temperature + 3 ºC
04
Setting Temperature + 1 ºC
Heating temperature
compensation
Models:
RPF(I)-FSN2E
O
00
RPF(I)-FSN2E: Normal
(factory setting)
(Setting Temperature + 2 ºC)
01
No compensation
(Setting Temperature)
02
Setting Temperature + 2 ºC
b2
Circulation function at
heating Thermo-OFF
O
00
Function disabled
(factory setting)
This function keeps the fan
running during the Thermo-OFF
sequence, at the fan speed set
on the remote control switch, to
prevent the stratication of air in 
the room.
01
Function enabled
b3
Forced compressor
operation for at least three
minutes
(Not available for models
KPI-E4)
O
00
Function disabled (factory setting):
Forced compressor operation for at
least three minutes can be enabled or
disabled through C7 setting
This function is used to allow
the setting of C7, to protect the
compressor by preventing it
from being started or stopped for
periods of less than 3 minutes.
01
Function enabled:
Forced compressor operation for at
least three minutes always occurs
independently of C7 setting
b4
Change of lter cleaning 
period
O
00
Standard (1200 hours)
This function is used to modify
the period of operation after
which the air lter cleaning 
indication is shown in the remote
control.
For RPK-FSR(H)M models,
the factory setting is b4=00:
Standard setting 200 hours.
01
100 hours
02
1200 hours
(factory setting)
03
2500 hours
04
No indication
b5
Locking of operation
mode
(Not available for models
KPI-E4)
X
00
Function disabled
(factory setting)
This function prevents the
modication of the operation 
mode of the unit from the remote
controller and from central
controls, once it has been
selected.
01
Function enabled
b6
Locking of setting
temperature
X
00
Function disabled
(factory setting)
This function prevents the
modication of the setting 
temperature of the unit from
the remote controller and from
central controls, once it has
been selected.
01
Function enabled