3 Electrical and control settings
Setting of DIP switches and RSW switches
SMGB0137 rev.0 - 05/2021
59
3
3.2  Setting of DIP switches and RSW switches
Cycle number 0
Cycle number 1
Cycle number 2
Terminal resistance
Number of refrigerant 
cycle (setting for the tens 
digit)
Number of refrigerant 
cycle (setting for the last 
units digit)
Outdoor units
Indoor units
Number of refrigerant 
cycle (setting for the last 
units digit)
Number of refrigerant 
cycle (setting for the 
tens digit)
Address of the indoor 
unit (setting for the tenth 
digit)
Address of the indoor 
unit (setting for the tenth 
digit)
1  TurnothepowersupplybeforesettingtheDIPswitches.Otherwise,theswitchsettingsareinvalid.
2  To set the position of the RSW rotary switches, insert a screwdriver into the groove of the RSW.
? NOTE
• TheDIPandRSWswitchesofeachindoorandoutdoorunitmustbeset.
• DSW5andRSW(1/2):refrigerantcyclenumbersetting/DSW6andRSW(1/2):Unitnumbersetting
WhenconsideringtheparDSW(5/6)/RSW(1/2)payattentionthattheRSWnumbersaredierentdependingontheindoorunitseries.
Pleasefollowthefollowingtables: