6 Commissioning
Test run procedure using the wireless remote control
SMGB0137 rev.0 - 05/2021
177
6
12 The operating temperature:
• Cooling operation
a. Indoor DB 21.5ºC and higher.
b. Indoor WB 16ºC and higher.
c. Outdoor DB 0ºC and higher.
• Heating operation
a. Indoor DB 27ºC and below.
13 Use shielded cables for the installation to avoid electrical noise. This must be less than 1000 m in length and meet
with national and local regulations.
14 Disconnect the KPI unit if it is connected to the indoor unit control. Otherwise the unit will not carry out the test run.
6.2 Test run procedure using the wireless remote control
From the remote controller switch can be carry out the test run procedure. Please follow the remote control switch
technical documentation for details.