7 Servicing
RPF(I)-(1.0-2.5)FSN2E - Floor and Floor concealed type
SMGB0137 rev.0 - 05/2021
269
7
7.8.6  Removal of the printed circuit board (PCB)
1  Remove the air inlet grille as indicated in section “7.8.1 Removal 
of the air inlet grille”.
2  Remove the air lter as indicated in section “7.8.2 Removal of the 
air lter”.
3  Remove the front panel as indicated in section “7.8.4 Removal of 
the front panel”.
4  Remove the side panel, removing the 3 set screws and pulling 
the panel downwards.
5  Remove the panel from the electrical box after removing the four 
set screws.
6  Remove the 2 set screws from the electrical box and release the 
attachment from the top of the box. Turn the electrical box at a 
90° angle.
Electrical box 
panel
Screw
7  Press the four attachment points of the PCB using long-tipped 
pliers and placing a nger next to the hole in the PCB before 
removing the PCB.
Rear side of 
the unit
Front side of 
the unit
! CAUTION
•  Do not touch the electrical components of the PCB.
•  Do not apply force to the PCB, as this could damage it.
•  Pay special attention to the position of the connectors on the PCB. An incorrect position during installation may damage the PCB
.
7.8.7  Removal of the thermistors from the liquid and gas piping
1  Remove the air inlet grille as indicated in section “7.8.1 Removal 
of the air inlet grille”.
2  Remove the air lter as indicated in section “7.8.2 Removal of the 
air lter”.
3  Remove the front panel as indicated in section “7.8.4 Removal of 
the front panel”.
4  Remove the side panel, removing the 3 set screws and pulling 
the panel downwards.
5  Disconnect the wiring from the thermistor and remove the 
thermistor.
Side panel