5 Optional functions
Complementary systems
SMGB0137 rev.0 - 05/2021
174
5.3.2  Econofresh Kit
 
Available ports
The system has three optional input signals programmed into the PCB using connector CN3 on the RPI unit and using 
the remote control. Connector CN3 has two ports for conguring the optional input signals of the Econofresh kit.
The outdoor cooling function E1 requires no CN3 connector setting.
? NOTE
When the RPI unit DSW6 is set for use of the Econofresh kit, CN3 connectors 1 and 2 are locked on the RPI unit PCB.
 
Description of optional input signals
Enthalpy sensor
On-screen display: E2.
The signal opens and closes the air inlet valves and the outlet damper, mixing the outdoor air and the return air of the 
Econofresh kit. This function is based on the air quality parameters that provide precise control of the air quality.
Connect the cables as indicated in point “5.1.1 Available ports”. Only CN3 contacts 1 and 2 can be connected.
The signal has the following control logic:
Connector Contact number X1 Damper valve
CN3 1, 2
ON —
OFF Enabled
CO
2
 sensor
On-screen display: E4.
This signal controls the inlet of outdoor air according to the concentration of CO
2
 inside the room.
Connect the cables as indicated in point “5.1.1 Available ports”. Only CN3 contacts 1 and 2 can be connected.
The signal has the following control logic:
Connector Contact number X1 Damper valve
CN3 1, 2
ON —
OFF Enabled
Compatibilities between optional signals
The following table shows the compatibility between the dierent optional signals:
PC-ARPFE 
optional 
functions
Room 
thermostat
Remote 
control 
thermistor
Remote 
thermistor
Wireless 
remote 
control
Outdoor 
cooling 
mode
Enthalpy 
sensor
CO
2
 
sensor
Room 
thermostat
– – – – – – – –
Remote 
control 
thermistor
C8
– – – – O O O
Remote 
thermistor
– – – – – – – –
Wireless 
remote control
– – – – – O O O
Outdoor 
cooling mode
E1
– O – O – – –
Enthalpy 
sensor
E2
– O – O – – –
CO
2
 sensor
E4
– O – O – – –
Not available: – 
Available: O