5 Optional functions
Complementary systems
SMGB0137 rev.0 - 05/2021
172
Conguration menu:
There are available the following congruation settings
Where Code Function KPI-E4E KPI-X4E DX Setting Status Remarks
PCB2
(PSW)
Ct
CO
2
sensor type O O -
00: ON/OFF CO
2
signal (*1)
01: Activated 4-20mA signal
02: Activated 0-10V signal
S1
Set minimum O O -
Range: 4-20 (Default= 01: 4)
or range: 0-10 (Default= 02: 0)
If Ct = 00
S1 will be “--“
S2
Set maximum O O -
Range: 4-20 (Default= 01: 20)
or range: 0-10 (Default= 02: 10)
If Ct = 00
S2 will be “--“
dF
Defrost Fan - O O
00: Fan Low operation (Default)
01: Fan kept operation
02: Fan stopped operation
of
O󰀨set for Thermo OFF 
conditions
O O O Range: 10 to 20 ºC Tset +- O󰀨set
Lo
Set low fan speed - - O Range: 20% to 99%
This function
establishes the duty
in order to x the fan 
speed, only
DX-Interface with EC
Fan conguration
St
Set medium fan speed - - O Range: 20% to 99%
H
Set high fan speed - - O Range: 20% to 99%
? NOTE
(*1): CO
2
sensor signal must be an ON/OFF signal. CO
2
sensor must be connected to CN3, pins 1-2, for i1 input signal (refer to outdoor
unit technical catalogue for further information about the connection specs).