6 Optional functions
Optional functions through Remote control
SMGB0099 rev.0 - 12/2016
210
Elem. Optional function
Individual
setting
Settings Setting conditions Description
b7
Fixing of operation as
exclusive cooling mode
only
X
00 Not activated function
This function is available to use
cooling mode only and to prevent
heating mode from being enabled.
01 Activated function
b8
Automatic COOL/HEAT
operation
X
00 Not activated function
This function allows the automatic
change from the cooling to the
heating mode for the units with the
same refrigerant cycle.
01 Activated function
b9 Fixing of fan speed X
00 Not activated function
Once the unit fan speed has been
selected, this function prevents from
being modied from the remote 
control.
01 Activated function
bA Not available X
“- -”
Permanent
Not available
bb
Cooling temperature
compensation due to
uneven load
X
00
Standard setting.
No compensation
This function is used to obtain longer
cooling periods.
01
It decreases the temperature
-1ºC
02
It decreases the temperature
-2ºC
bC Not available
00
Not available
Use at 00 conditions
01
bd Not available
00
Not available
Use at 00 conditions
01
bE Not available
00
Not available
Use at 00 conditions
01
C1 Not available
00
Not available
Use at 00 conditions
01
C2 Not available
“- -”
Permanent
Not available
C3 Not available O
00
Not available
Use at 00 conditions
01
C4
Drain pump in
heating mode
O
00 Not activated function
This function is used to activate the
drain pump in heating mode.
Not available for models:
RCIM-FSN4(E)
RCD-FSN3
01 Activated function
C5
Static pressure selection
Models
RPI-FSN4E
RPIM-)FSN4E(-DU)
RPI-FSN3(P)E
O
00
Standard static pressure (factory
set)
This function is used to change the
static pressure of the RPI units from
the remote control.
01 High static pressure
02 Low static pressure
Increasing fan speed
Models
RPC-FSN3E
RPF(I)-FSN2E
RCI-FSN4
RPC-FSN3
RPK-FSN3M
RCD-FSN3
RCIM-FSN4(E)
O
00 Not available
This function is used to change the
indoor units fan speed installed in
high ceilings.
01 Hi Speed 1
(2)
02 Hi Speed 2
(2)
C6
Hi speed at heating
Thermo-OFF
O
00 Not activated function
This function is used to increase
the fan speed when the thermostat
reaches the set temperature in
heating using function C5.
01 Activated function

Table of Contents

Other manuals for Hitachi RCIM-1.5FSN4

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Hitachi RCIM-1.5FSN4 and is the answer not in the manual?

Hitachi RCIM-1.5FSN4 Specifications

General IconGeneral
BrandHitachi
ModelRCIM-1.5FSN4
CategoryAir Conditioner
LanguageEnglish

Related product manuals