2 Unit installation
DX-Interface
SMGB0099 rev.0 - 12/2016
76
4 Secure proper space around the control box and expansion valve box for operation and maintenance work. Also a
service access door should be prepared in order to remove the DX-interface without getting rid of the ceiling plate.
5 Select a suitable and convenient location for the refrigerant piping connection.
6 Do not install the DX-Interface in a kitchen where vapour or mist ows. Dew condensation water may occur on the
expansion valve box while cooling operation. In this case, use the insulation.
7 Do not install the DX-Interface in a organic solvent (thinner or benzine) environment. Synthetic resin parts may
dissolve.
8 Do not install the DX-Interface where generation, owing or staying of ammable gas may occur.
9 The sound of refrigerant running through from the expansion valve box may be heard. Therefore install the expansion
valve box where the sound will not leak such as in the false ceiling of a hall way.
10 Use ceiling material with sound-proof such as plaster board.
2.12.3 Mounting method
bc
da
1
.8
N
4
? NOTE
In case of installation positions “c” and “d”, make sure to insulate the copper pipes inlet on the expansion valve box cover to avoid any
liquid ltration and accumulation.
Minimum sizes (mm).