6 Optional functions
Optional functions through Remote control
SMGB0099 rev.0 - 12/2016
216
Elem. Optional function
Individual
setting
Settings Setting conditions Description
K5
Human sensor detection
level
Models
RCD-FSN3
RCIM-FSN4(E)
RCI-FSN4
RPC-FSN3
–
00 Standard
01 High
02 Low
K6
Selection of available
operation modes upon
selection of either remote
control thermo or remote
sensor
Models
RCD-FSN3
RCIM-FSN4(E)
O
00 ALL
01 COOL/DRY
02 HEAT
03 ALL
? NOTE
When a particular model is not specied, the Optional functions described in the above table are suitable for all the models in this manual.
O: allows for individual setting.
X: the setting is made for all outdoor units.
–: not used.
(1)
Setting 02 is not available on all indoor units.
(2)
On RPI units: 00 Increases speed 1 (standard), 01 Increases speed 2 (high static pressure), 02 Standard speed (low
static pressure).
(3)
00 standard (7-step operation); 01 draft prevention (cannot be set below two steps); 02 High ceilings (cannot be set
above two steps).
(4)
In case that the set temperature is changed and kept within the set time at “F4”, the temperature is automatically
changed to “F5” and “F6”. In case that the set temperature is out of range at “F5” and “F6”, it is applied within upper
and lower limit for the set temperature.
(5)
Operation is stopped by pressing the run/stop switch for 3 seconds.
(6)
When the unit is restarted by the remote control switch, the temperature automatically changes to the setting
temperature of “F5” or “F6”.
? NOTE
• Makes the changes to the optional settings at least three minutes following start-up.
• On modifying the ”CF” (air outlet louver angle change) setting, restore the power supply or allow the automatic louver to make a full
cycle in automatic mode to apply the optional setting.
• The optional function settings are different depending on the indoor or outdoor units. Check that the unit has the optional setting.
• Save the optional settings made on each outdoor and indoor unit in the “Setting” column of the table.