Chapter 8 Mandatory Setting for Motor Drive and Test Run
8-2-2
When operating by inputting RUN command and frequency command from the keypad
(1) Before test run, confirm that each parameter is set correctly according to "8.1 Mandatory
Setting for Operation".
(2) Set [F001], [F004], [A001], and [A002] as shown in the table below.
It is recommended that "Output frequency setting or monitor [F001]" is set to a low speed of
approximately 10 Hz for safety at the first time.
The default setting of "Acceleration time 1 setting or monitor, 1st-motor
[F002]"/"Deceleration time 1 setting or monitor, 1st-motor [F003]" is 10 seconds. Please
change as necessary. In addition, V/f control is recommended for "Control mode selection,
1st-motor [A044]" in the test run with no load.
(3) Monitor the output frequency with [d001] and confirm that "0.00" (Hz) is displayed.
(4) When the RUN key is pressed, the running LED [RUN] of keypad lights and the motor starts to
rotate.
(5) Check there are any abnormalities in output frequency monitor, actual motor rotation speed,
motor rotation direction, and inverter. The motor rotation direction can be checked by
"Rotation direction monitor [d003]".
(6) If no problem is found, gradually increase the output frequency by [F001].
(7) After checking the operation, press STOP/RESET key. The motor starts decelerating and after
stopping, the running LED [RUN] on keypad turns off.
Code
Item
Description
Data
[d001]
Output frequency
monitor
Displays the output frequency of the
inverter.
0.00 to
Maximum frequency
[d003]
Rotation direction
monitor
Displays the operation direction of the
inverter.
F (forward)/ r (reverse)/
o (stop)
[F001]
Output frequency
setting or monitor
Set the output frequency command to
the motor.
0.0, Minimum frequency
to Maximum frequency
[F002]
Acceleration time 1
setting or monitor,
1st-motor
Set the acceleration time/deceleration
time as necessary. The default value is
10.0 (s).
0.00 to 3600.00 (s)
[F003]
Deceleration time 1
setting or monitor,
1st-motor
[F004]
RUN-key command
rotation direction
Set the rotation direction when
operating with keypad's RUN-key.
00(Forward)/ 01(Reverse)
[A001]
Frequency input
source selection
Operates with the frequency reference
set in "Output frequency setting or
monitor".
02
[A002]
RUN command input
source selection
Starts rotation by pressing keypad's
RUN-key.
02
[A044]
Control mode
selection
Operates with the constant torque
characteristics of V/f control.
00
Lights when start operation by
RUN-key.
When RUN command source is
keypad, the RUN-key is enabled
and the RUN command
indicator LED lights.
Lights up when the frequency
data is displayed.