Chapter 9 Inverter Functions
9-7-10
9.7.7 Selecting Stop Operation
How to perform a free run stop to avoid overvoltage trips from occurring during deceleration
due to significant load inertia?
How to shut-off output from the inverter immediately as a mechanical brake is used for
stopping?
Use "STOP mode selection [b091]" to choose either to stop the inverter by decelerating to a
stop according to the deceleration time setting, or by putting the inverter in a free run state by
immediately shutting off inverter output.
To perform a free run stop using the control circuit terminal input signal, assign "Free run stop
[FRS] (11)" to one of the input terminals.
If the inverter performs a free run stop, the next startup when an RUN command is input will
follow the selection made for "Restart mode after FRS release [b088]".
When "Free run stop (01)" is selected for [b091], the inverter output is shut off at the timing
when the RUN command is turned off, and the motor will start idling.
Code
Item
Description
Data
[b091]
STOP mode selection
The inverter decelerates to a stop as normal when
stopping.
00
Inverter output is shut off to perform a free run stop when
stopping.
01
[C001]
to
[C007]
Input terminal function
Free run stop [FRS]:
When this signal is turned on, inverter output is shut-
off to perform a free run stop.
11
(Example 1) Example of operation when the
"STOP mode selection [b091]" is
set to "Free run stop (01)"
(Example 2) Example of operation when the [FRS]
terminal is turned off
Free running
Restart according to
"Restart mode after FRS release [b088]".
Motor speed
RUN
command
Free run stop
[FRS]
ON
RUN
command
ON
OFF
Free running
Restart according to
"Restart mode after FRS release [b088]".
Motor speed
A
!
Q