Chapter 5 Wire Connection
5-4-9
5.4.3 Switching Sink/Source Logic and Connecting External Power
Supply/Programmable Controller
How can the sink/source logic of the I/O terminals be switched?
How can an external power supply or external devices such as a programmable controller (PLC)
be connected to the I/O terminals?
Method of switching sink/source logic for intelligent input terminals
To switch the logic of the input terminals to source logic, remove the short-circuit wire between
[P24] terminal and [PLC] terminal on the control terminal and connect it between [PLC] terminal
and [L] terminal. (The factory default of the logic depends on the destination region.)
Refer to the figure below for wiring when using an external power supply and wiring with
external devices such as programmable controllers.
Connecting the intelligent input terminals to a programmable controller
Sink logic
When using the inverter's internal power supply
When using an external power supply
(Remove the short-circuit wire from the control terminal.)
Source logic
When using the inverter's internal power supply
When using an external power supply
(Remove the short-circuit wire from the control terminal.)
24 VDC
S
P24
Short-circuit
wire
PLC
L
1
7
COM
Inverter
Output module
(EH-YT**, etc.)
24 VDC
P24
PLC
L
1
S
7
24 V
DC
COM
Output module
(EH-YTP**, etc.)
Inverter
24 VDC
PLC
L
1
Short-
circuit
wire
7
S
Output module
(EH-YT**, etc.)
Inverter
COM
P24
COM
P24
24 VDC
PLC
24 VDC
L
1
7
S
Inverter
Output module
(EH-YTP**, etc.)
Short-circuit
wire
PLC
P24
L
1
2
Sink logic
Short-circuit
wire
PLC
P24
L
1
2
Source logic
(Factory default setting)