Chapter 9 Inverter Functions
9-12-4
9.12.4 Outputting a Signal When Inverter Is Ready to Run
How can I inform the system that the inverter is ready to operate with a RUN command?
Assigning "Inverter ready [IRDY] (50)" to one of the output terminal functions
([C021]/[C022]/[C026]) enables the inverter to output an inverter ready signal.
The [IRDY] signal is output when the inverter is ready to accept a RUN command.
The system does not function even if RUN commands are input if this signal has not been
output.
This signal remains off while output is unavailable, such as during startup preparations when
turning the power on, undervoltage, tripping, a free-run stop command is issued, STO is
activated, and other circumstances.