Chapter 15  Tips/FAQ/Troubleshooting 
15-3-1 
15.3 
Troubleshooting for Warning Functions Related Error  
 
15.3.1 Warning Display 
 
  How to know the cause of the warning and troubleshooting when a warning occurs? 
 
  If the set parameter is inconsistent with another set value, a warning is displayed and the 
program LED [PRG] blinks. 
  Warning displays and their conditions are shown below. If a warning is displayed, correct the 
parameter referring to the contents of the table. (Even if RUN command is given, it is not 
automatically rewritten to the correct value.) 
  The latest warning message is stored in "Warning monitor [d090]". If no warning has occurred,   
" " is displayed. 
 
Warning display condition 
Upper frequency limit, 1st-motor [A061] 
Maximum frequency, 1st-motor [A004] 
Lower frequency limit, 1st-motor [A062] 
Maximum frequency, 1st-motor [A004] 
Output frequency setting or monitor 
[F001], Multi-speed 0, 1st-motor [A020] 
Maximum frequency, 1st-motor [A004] 
Output frequency setting or monitor 
[F001], Multi-speed 0, 1st-motor [A020] 
Upper frequency limit, 1st-motor [A061] 
Lower frequency limit, 1st-motor [A062] 
Output frequency setting or monitor 
[F001], Multi-speed 0, 1st-motor [A020] 
Minimum frequency adjustment [b082] 
Upper frequency limit, 1st-motor [A061] 
Minimum frequency adjustment [b082] 
Lower frequency limit, 1st-motor [A062] 
Minimum frequency adjustment [b082] 
Output frequency setting or monitor 
[F001], Multi-speed 0, 1st-motor [A020] 
Minimum frequency adjustment [b082] 
Output frequency setting or monitor 
[F001], Multi-speed 0, 1st-motor [A020] 
Jump frequency ± Jump frequency width 
([A063] ± [A064], [A065] ± [A066], [A067] 
± [A068])
*1
 
Multi-speed 1 to 15 [A021] to [A035] 
Free-V/f frequency 7 [b112] 
Upper frequency limit, 1st-motor [A061] 
Free-V/f frequency 7 [b112] 
Lower frequency limit, 1st-motor [A062] 
Free-V/f frequency 7 [b112] 
Output frequency setting or monitor 
[F001], Multi-speed 0, 1st-motor [A020] 
Upper Frequency limit, 2nd-motor 
[A261] 
Maximum frequency, 2nd-motor [A204] 
Lower Frequency limit, 2nd-motor [A262] 
Maximum frequency, 2nd-motor [A204] 
Output frequency [F001], 2nd multi-
speed 0-speed [A220] 
Maximum frequency, 2nd-motor [A204] 
Output frequency [F001], 2nd multi-
speed 0-speed [A220] 
Upper Frequency limit, 2nd-motor [A261] 
Lower Frequency limit, 2nd-motor [A262] 
Output frequency [F001], 2nd multi-
speed 0-speed [A220] 
Minimum frequency adjustment [b082] 
Upper Frequency limit, 2nd-motor [A261] 
Minimum frequency adjustment [b082] 
Lower Frequency limit, 2nd-motor [A262] 
Minimum frequency adjustment [b082] 
Output frequency [F001], multi-speed 0-
speed [A220] 
Output frequency [F001], 2nd multi-
speed 0-speed [A220] 
Jump frequency ± Jump frequency width 
([A063] ± [A064], [A065] ± [A066], [A067] 
± [A068])
*1
 
Free-V/f frequency 7 [b112] 
Upper Frequency limit, 2nd-motor [A261] 
Free-V/f frequency 7 [b112] 
Lower Frequency limit, 2nd-motor [A262] 
Free-V/f frequency 7 [b112] 
Output frequency [F001], 2nd multi-
speed 0-speed [A220] 
*1. A warning occurs when the frequency settings of [F001], [A020], [A220], [A021] to [A035] are within the 
frequency range set in the jump frequency.