Chapter 11 RS485 Communication
11-3-3
List of 2 register length parameters accessible as 1 register length
Code
Item
Register
No.
R/W
Data range
Data
resolution
[d001]
Output frequency monitor
1E21h
R
0 to 59000
0.01 (Hz)
[d004]
PID feedback value monitor
1E22h
R
0 to 65535
0.01
[d007]
Output frequency scale
conversion monitor
1E23h
R
0 to 65535
0.01
[d008]
Detect speed monitor
1E24h
R
32768 to +32767
0.01 (Hz)
[d081]
Trip monitor 1
Output frequency
1E25h
R
0 to 59000
0.01 (Hz)
[F001]
Output frequency setting or
monitor
1F31h
R/W
0, Min. to Max. frequency
0.01 (Hz)
[F002]
Acceleration time 1 setting or
monitor, 1st-motor
1F32h
R/W
0 to 65535
0.01 (s)
[F003]
Deceleration time 1 setting or
monitor, 1st-motor
1F33h
R/W
0 to 65535
0.01 (s)
[A020]
Multi-speed 0, 1st-motor
1F34h
R/W
0, Min. frequency to
Maximum frequency, 1st-
motor
0.01 (Hz)
[A021]
Multi-speed 1
1F35h
R/W
0, Min. to Max. frequency
0.01 (Hz)
[A022]
Multi-speed 2
1F36h
R/W
0, Min. to Max. frequency
0.01 (Hz)
[A023]
Multi-speed 3
1F37h
R/W
0, Min. to Max. frequency
0.01 (Hz)
[A061]
Upper frequency limit, 1st-
motor
1F38h
R/W
0, Lower frequency limit,
1st-motor to Max.
frequency, 1st-motor
0.01 (Hz)
[A062]
Lower frequency limit, 1st-motor
1F39h
R/W
0, Min. frequency to
Upper frequency limit,
1st-motor
0.01 (Hz)
[A069]
Acceleration stop frequency
1F3Ah
R/W
0 to 59000
0.01 (Hz)
[A145]
ADD frequency
1F3Bh
R/W
0 to 59000
0.01 (Hz)
[A154]
Deceleration stop frequency
1F3Ch
R/W
0 to 59000
0.01 (Hz)
[A156]
PID sleep start level
1F3Dh
R/W
0 to 59000
0.01 (Hz)
[b007]
Frequency matching minimum
restart frequency
1F3Eh
R/W
0 to 59000
0.01 (Hz)