Chapter 18 List of Parameters/Modbus Coil/Register Numbers
18-2-15
[Ai2] operation
set level at
disconnection or
compare event
0 to 100 (%) / no: Disable
Accumulated
input power
monitor clear
00: Disable
01: Clear (return to 00 after
clearing)
Display gain for
the accumulated
input power
monitor
0.01 to 10.00 (Hz)
(100.00 (Hz))
*3
2.0 to 15.0 (kHz) (Normal duty (ND))
2.0 to 10.0 (kHz) (Low duty (LD))
(2.0 to 10.0 (kHz))
*3
* With derating.
20 to 150 (ND)
20 to 100 (LD)
(20 to 100)
*3
Initialize mode
selection
00: Disable
01: Trip history
02: Parameter initialize
03: Trip history and parameter
04: Trip history, parameter
and EzSQ
Initialize data
selection
00: Pattern 0
01: Pattern 1
03: Pattern 3
Frequency
conversion gain
00: Enable
01: Disable
02: Enable at only trip reset
Restart mode
after FRS release
00: 0Hz start
01: Restart with frequency
matching
02: Active frequency matching
restart
Automatic carrier
reduction
selection
00: Disable
01: Enable: Current
02: Enable: Temperature
0.0 to 100.0(%)
* Depends on b097 setting.
00: Deceleration stop
01: Free run stop
Cooling fan
control method
selection
00: Always
01: While inverter operates (3
minutes after power on
and run stop)
02: Depends on temperature
Accumulated
cooling fan run
time clear
Initialize target
selection
00: All parameters
01: All parameters except
terminal and
communication
configuration
02: Parameters registered in
[U***]
03: All parameters except
parameters registered in
[U***] and [b037]
Dynamic brake
activation
selection
00: Disable
01: Enable only while running
02: Enable always
*2. The default settings when initialize by setting 00/01/03 to "Initialize data selection [b085]".
*3. When in WJ200 high frequency compatible mode.