Chapter 18 List of Parameters/Modbus Coil/Register Numbers
18-2-17
Overvoltage
suppression
active level
200V class: 330 to 400 (VDC)
400V class: 660 to 800 (VDC)
330 to 400 (200V)
660 to 800 (400V)
Overvoltage
suppression
active time
Constant DC bus
voltage control P
gain
Constant DC bus
voltage control I
gain
00: No trip (only shut down by
hardware)
01: [E37] trip
02: [E98] trip, display [-S--]
03 (04): Display [-S--]
(03 and 04 are the same
in terms of function.)
05: Display [-S--]/[-F**]
06: Display [-S--]/[-F**]
STO release
delay allowed
time
STO special
indication cancel
selection
00: Not cancel special
indication
01: Cancel special indication
STO special
indication re-
display time
Display while ext.
operator
connected
001 to 060 (compatible with
d001 to d060)
001 to 030 (compatible with
d001 to d030)
001 to 030 (compatible with
d001 to d030)
Enable frequency
changes through
monitor display
00: Disable
01: Enable (frequency setting
can be changed in
[d001]/[d007]
Enable auto-
return to the
initial display
Action selection
at ext. operator
disconnection
00: Trip
01: Trip after deceleration stop
02: Ignore
03: Free run
04: Deceleration stop
00: Enable R/W
01: Disable R/W
00: Disable
01: IM mode
02: (WJ200 high frequency
compatible mode)
*3
03: PM mode
Execute
initialization and
mode selection
00: Disable
01: Execute initialization and
mode selection
Password setting
for display
restriction
selection [b037]
0000(Password disable),
0001 to FFFF (Password
enable)
*2. The default settings when initialize by setting 00/01/03 to "Initialize data selection [b085]".
*3. When in WJ200 high frequency compatible mode.