Chapter 5 Wire Connection
5-3-3
Three-phase 400 V model
Model
Load rating setting
Main circuit
terminal block
wiring
AWG (mm
2
)
Terminal
screw size
(Terminal
block width)
Crimp terminal
Power/Ground
Tightening torque
Nm
Power/Ground
(maximum value)
C1-004HF
Normal duty (ND)
AWG16
(1.3 mm
2
)
M4
(9.9 mm)
R2-4/R2-4
1.4/1.3 to 1.5
(1.6/1.8)
Low duty (LD)
C1-007HF
Normal duty (ND)
AWG16
(1.3 mm
2
)
M4
(9.9 mm)
R2-4/R2-4
1.4/1.3 to 1.5
(1.6/1.8)
Low duty (LD)
C1-015HF
Normal duty (ND)
AWG16
(1.3 mm
2
)
M4
(9.9 mm)
R2-4/R2-4
1.4/1.3 to 1.5
(1.6/1.8)
Low duty (LD)
C1-022HF
Normal duty (ND)
AWG14
(2.1 mm
2
)
M4
(9.9 mm)
R2-4/R2-4
1.4/1.3 to 1.5
(1.6/1.8)
Low duty (LD)
C1-030HF
Normal duty (ND)
AWG14
(2.1 mm
2
)
M4
(9.9 mm)
R2-4/R2-4
1.4/1.3 to 1.5
(1.6/1.8)
Low duty (LD)
C1-040HF
Normal duty (ND)
AWG12
(3.3 mm
2
)
M4
(9.9 mm)
R5.5-4/R5.5-4
1.4/1.3 to 1.5
(1.6/1.8)
Low duty (LD)
C1-055HF
Normal duty (ND)
AWG10
(5.3 mm
2
)
M5
(13 mm)
R5.5-5/R5.5-5
3.0/3.0
(3.0/3.0)
Low duty (LD)
C1-075HF
Normal duty (ND)
AWG10
(5.3 mm
2
)
M5
(13 mm)
R5.5-5/R5.5-5
3.0/3.0
(3.0/3.0)
Low duty (LD)
C1-110HF
Normal duty (ND)
AWG6
(13 mm
2
)
M6
(16.5 mm)
R14-6/R14-6
3.9 to 5.0/3.9 to 5.0
(5.2/5.2)
Low duty (LD)
C1-150HF
Normal duty (ND)
AWG6
(13 mm
2
)
M6
(16.5 mm)
R14-6/R14-6
3.9 to 5.0/3.9 to 5.0
(5.2/5.2)
Low duty (LD)
The wire size in the above table shows the designed values based on HIV cables (with thermal
resistance of 75°C).
If the wiring length exceeds 20 m, a thick power line needs to be used.
When connecting wires to the main circuit terminal block, use round crimping terminals (UL-
certified item) suitable for the wires for use. Use a crimp tool recommended by the
manufacturer of the crimping terminal to crimp the terminal.
Use a ground wire with a diameter equal to or thicker than that indicated on the power line.
It is recommended to tight screws at the "maximum value" of the tightening torque in the above