E-Mon® Series Global User Manual
Safety Information
Page | 8
54-000-01-ENG01-0121
1.4. Installation Safety Instructions
The installation involves high voltage as well as various equipment/elements/connection
points/exposed zones capable of delivering powerful electrical shocks. Users are advised to
follow caution while handling the equipment setup.
Before any installation or maintenance work, disconnect the unit from all voltage
sources and make sure that there are no exposed dangerous wires.
AC supply units must be disconnected from the adjacent low-voltage networks and
marked with a separator using switch or circuit breaker.
The device shall be available in disconnected condition in the final product.
Only trained personnel shall perform installation and configuration and must be
carried out in accordance with the national and international standards.
The installer shall use conduit fittings that maintains the environmental rating of type
4 when installing the CS and meter in polymeric enclosure type 4.
Ensure all low voltage inputs are protected from hazardous live wires by double or
reinforced insulation.
During installation, make sure that the power supply and wiring of the output contacts
are supplied by the same mains phase so that max permissible voltage shall not
exceed.
Insulation to surrounding components should be evaluated after installation in the
end-product.
To reduce risk of electric shock, always open/disconnect the monitored circuit from
power-distribution system before installing current-sensors.
The terminals shall be closed using appropriate POZIDRIV no. 1 with approximately
0.8 Nm torque.
Unused terminals must be sealed with maximum torque to avoid loosening and
exposure. Please refer to the technical data sheet.
Use only shielded cable for signal and control lines. Apply cable shielding on both
sides. Flying leads minimum cross-section 0.14 mm
2
.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell E-Mon EM3S-V-P-R and is the answer not in the manual?

Honeywell E-Mon EM3S-V-P-R Specifications

General IconGeneral
BrandHoneywell
ModelE-Mon EM3S-V-P-R
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals