MS-5UD & MS-10UD Series Manual — P/N 52626:C7 6/12/2018 55
Master Programming Level Programming
Type
To select the type of zone being programmed, press the 2 key while viewing the Edit Input Zone Screen #2. This will cause the control
panel to display the following Zone Type Screen:
Pressing the down arrow key will display additional zone types as indicated in the following table.
Some of the following Zone Types are not available for Canadian applications. Refer to “Canadian Option” on page 70 for additional
details.
While viewing any Zone Type screen, select the type of zone being programmed by pressing the corresponding keyboard number key.
The display will return to Edit Input Zone Screen #2 and indicate the selection next to the Type option.
Zone Type Action When Activated
Pull-Station Fire Alarm
Waterflow Fire Alarm Delayed (uses waterflow delay)
Waterflow Nonsilenceable Fire Alarm (uses waterflow delay)
Combo Fire/Supervisory (uses waterflow delay)
Combo AutoResettable Fire/Supervisory AR, nonlatching (uses waterflow delay)
2-Wire Detector Fire Alarm
Normally Open Contact Fire Alarm
Fire Fire Alarm
Tamper Supervisory
Supervisory Supervisory, latching
Supervisory AutoResettable Supervisory, nonlatching
Medic-Alert Supervisory, latching
Hazard-Alert Supervisory, latching
Tornado-Alert Supervisory, latching
Proc-Mon Piezo
Procmon-AR Piezo, nonlatching
AC-Loss-Mon Trouble
Ack-Switch Acts like panel Acknowledge Key
Sil-Switch Acts like panel Alarm Silence Key
Drill-Switch Acts like panel Drill Key
Reset-Switch Acts like panel Reset Key
PAS-Bypass Positive Alarm Sequence Disable
Drill-Switch AutoResettable Acts like panel Drill Key, nonlatching
Table 3.1 Zone Types
ZONE TYPE
1=PULL STATION
2=WATERFLOW
3=WATERFLOW NS
Zone Type Screen #1
NOTE: Almost any Input Zone type can activate an ACC-25/50ZST audio zone and output an assigned message with the exception of
ACKNOWLEDGE, SILENCE, RESET and PAS BYPASS Switches. The DRILL Switch (or input programmed as a drill switch) will cause all
of the corresponding ACC-25/50ZST audio zones to go active and will output Message 1.