MS-5UD & MS-10UD Series Manual — P/N 52626:C7 6/12/2018 59
Master Programming Level Programming
PAS
The PAS (Positive Alarm Sequence) option will program the zone to delay panel activation (including alarm relay and communicator)
for a period of 15 seconds plus a programmable time of up to 3 minutes. To enable the PAS feature, press 3 while viewing the PAS/Pre-
Signal Screen. This option is available only for circuits programmed as smoke detector circuits. Refer to “Positive Alarm Sequence” on
page 100.