MS-5UD & MS-10UD Series Manual — P/N 52626:C7 6/12/2018 85
Master Programming Level Programming
Ademco Contact ID Format - Primary Central Station Phone Number
The information shown in Table 3.4 is automatically programmed for the Primary Central Station phone number Event Codes when
Ademco Contact ID Format is selected. To disable event reporting, select the desired Event Code to be disabled and press 0 or Clear and
then Enter to disable it. (Enter must be pressed to save the selection. Pressing Escape will not save the selection).
Event Description
Event Code Settings
Zone Code
Active
Primary # Zone 1 - 10 Alarm 115 001 - 010
Primary # Zone 1 - 10 Disabled 570 001 - 010
Primary # Drill 604 000
Primary # AC Fault 301 000
Primary # Zone 1 - 10 Fault 380 001 - 010
Primary # Zone 1 - 10 Dirty 380 001 - 010
Primary # Earth Fault 310 000
Primary # Low Battery Fault 302 000
Primary # No Battery Fault 311 000
Primary # Telco Primary Line Fault 351 001
Primary # Telco Secondary Line Fault 352 002
Primary # NAC #1 Fault 321 001
Primary # NAC #2 Fault 322 002
Primary # NAC #3 Fault 326 003
Primary # NAC #4 Fault 327 004
Primary # NAC #1 Disable 521 001
Primary # NAC #2 Disable 522 002
Primary # NAC #3 Disable 526 003
Primary # NAC #4 Disable 527 004
Primary # Charger Fault 300 000
Primary # Comm Trouble Primary # 354 001
Primary # Comm Trouble Secondary #
354
002
Primary # Printer Fault
336
000
Primary # ANN-Bus Fault
330
000
Primary # Option Card Fault 333 000
Primary # CS CALC Fault 304 000
Primary # System Off Normal 308 000
Primary # System Test Message 602 000
Primary # System Abnormal Test Message 608 000
Primary # Upload/Download Request 411 000
Primary # Upload Successful 416 000
Primary # Download Successful 412 000
Primary # Upload/Download Failed 413 000
Primary # Voice EVAC Fault 330 000
Primary # Power Supply Sync Fault 300 000
Table 3.4 Ademco Contact ID Primary # Event Codes