MS-5UD & MS-10UD Series Manual — P/N 52626:C7 6/12/2018 87
Master Programming Level Programming
SIA-DCS Format - Primary Central Station Phone Number
The information shown in Table 3.6 is automatically programmed for the Primary Central Station phone number Event Codes when
SIA-DCS Format is selected. To disable event reporting, select the desired Event Code to be disabled and press 0 or Clear and then
Enter to disable it. (Enter must be pressed to save the selection. Pressing Escape will not save the selection).
Event Description
Event Code Settings
Active Restoral
Primary # Zone 1 Alarm FA1 FH1
Primary # Zone 2 Alarm FA2 FH2
Primary # Zone 3 Alarm FA3 FH3
Primary # Zone 4 Alarm FA4 FH4
Primary # Zone 5 Alarm FA5 FH5
Primary # Zone 6 Alarm FA6 FH6
Primary # Zone 7 Alarm FA7 FH7
Primary # Zone 8 Alarm FA8 FH8
Primary # Zone 9 Alarm FA9 FH9
Primary # Zone 10 Alarm FA10 FH10
Primary # Zone 1 Disabled FB1 FU1
Primary # Zone 2 Disabled FB2 FU2
Primary # Zone 3 Disabled FB3 FU3
Primary # Zone 4 Disabled FB4 FU4
Primary # Zone 5 Disabled FB5 FU5
Primary # Zone 6 Disabled FB6 FU6
Primary # Zone 7 Disabled FB7 FU7
Primary # Zone 8 Disabled FB8 FU8
Primary # Zone 9 Disabled FB9 FU9
Primary # Zone 10 Disabled FB10 FU10
Primary # Drill FI FK
Primary # AC Fault AT AR
Primary # Zone 1 Fault FT1 FJ1
Primary # Zone 2 Fault FT2 FJ2
Primary # Zone 3 Fault FT3 FJ3
Primary # Zone 4 Fault FT4 FJ4
Primary # Zone 5 Fault FT5 FJ5
Primary # Zone 6 Fault FT6 FJ6
Primary # Zone 7 Fault FT7 FJ7
Primary # Zone 8 Fault FT8 FJ8
Primary # Zone 9 Fault FT9 FJ9
Primary # Zone 10 Fault FT10 FJ10
Primary # Zone 1 Dirty FT1 FJ1
Primary # Zone 2 Dirty FT2 FJ2
Primary # Zone 3 Dirty FT3 FJ3
Primary # Zone 4 Dirty FT4 FJ4
Primary # Zone 5 Dirty FT5 FJ5
Primary # Zone 6 Dirty FT6 FJ6
Primary # Zone 7 Dirty FT7 FJ7
Primary # Zone 8 Dirty FT8 FJ8
Primary # Zone 9 Dirty FT9 FJ9
Primary # Zone 10 Dirty FT10 FJ10
Primary # Earth Fault ET38 ER38
Primary # Low Battery Fault YT0 YR0
Primary # No Battery Fault YT0 YR0
Table 3.6 SIA-DCS Primary # Event Codes