MAx panel Fire Detection System
M-167.3-Serie-MA-EN / 11.2021 17
3. Verify count: change the line reliability parameters
Invalid Reply: enter the parameter to report the fault for invalid
reply (expressed in number of interrogatio
n polling on the line).
-ID: enter the parameter to signal type ID invalid fault
(expressed in number of interrogation polling on the line).
-C: enter the parameter to signal open circuits fault
(expressed in number of interrogation polling on the line).
enter the value to signal a fault for smoke detector
low chamber value (expressed in number of interrogation
poll
ing on the line). Default value= 20
enter the parameter to signal the maintenance
shutdown. (expressed in minutes). Default value = 216.
To change one or more parameters in this folder, select the parameter using the arrow buttons (the
characters of the selected field are highlighted), press the enter button and use the arrow buttons to
change the parameter. When you have finished, press the enter button to confirm the values.
Increasing the values of each parameter will make the control unit less sensitive for the fault signalling for the
points installed on the lines.
Decreasing the values of each parameter will make the control unit more sensitive for the fault signalling for the
points installed on the lines, and the fault warning message will be activated: “Line changed par.”
4. Sounder: this tab is dedicated to programming the siren outputs (all devices programmed with SW TYPE ID
SND). The user can program the following items:
Sounders active on correlation: if this function is enabled, when
there is an
alarm siren
associated with this zone will be activated
only
if
the programmed correlation number for the alarm zone is
reached (see ZONE programming paragraph).
: sound tones in the event of an
alarm from
addressed devices (
values from 1 to 32 permitted
. For details,
refer to the technical data sheets
for the sirens).
in the event of an
alarm from addressed devices
(
values from 1 to 4 permitted. For more details, refer to
the
technical data sheets
for the sirens).
sound tone when activating the central
evacuation control (
values from 1 to 32 permitted.
For more
details, refer to
the technical data sheets for the sirens).
values from 1 to 4 permitted. For more
details, refer to the technical data sheets for the sirens).
Print tab: to access the list of options dedicated to printing events.
of the history log.
analogue values of the programmed sensors
alarm points in progress.
pre-alarm points in progress.
zone in faults in progress.
excluded points.
active input modules.
Prints the list of active output modules.