MAx panel Fire Detection System
26 M-167.3-Serie-MA-EN / 11.2021
6 TEST MENU
By pressing the TEST function button in the main system state
display, you can access the test menu, which includes the
functions generally used by the servicing personnel to test the
system.
To access the menu, enter the
level 2 password (22222
is the
default password).
To enter the password, refer to the editing function previously
mentioned in the paragraph describing keyboard operation to
enter data.
This menu is displayed.
Zones
This function allows you to start the walk-test procedure for a selected zone.
This procedure has two folders where the editing function previously explained is used to enter data.
Enabling of a zone for the test function:
Enter the zone number for which the test function needs to be
activated.
(0 = test zone OFF)
CBE enabling
Select CB
E Enable: YES
In the event of an alarm from the test zone devices
CBEs associated with them are activated
To change values in this folder, select the parameter using the
arrow buttons

(the characters of the selected field are
highlighted), press the enter button
and use the arrow buttons
to change the parameter. When you have finished, press the
enter button to confirm the entry.
Output selection
The output to be activated in the event of an alarm from a device in the test zone is selected in the subsequent
programming folder.
In the “Select” field you can select one of the following items:
NONE: in the event of an alarm from the test zone, no outputs are
activated.
SOUNDER: in the event of an alarm, both the siren output and all
the output modules programmed via SW TYPE ID
HORN
are
activated on every alarm event from the test zone. The activation
duration is three seconds.
MODULE: in the event of an alarm from the test zone, the output
module programmed in the
“Ind. Mod.
option is activated and
on every alarm event it will be active for three seconds.
To change one or more parameters in this folder, select the
parameter using the arrow buttons

(the characters of the
selected field are highlighted), press the enter button
and use
the arrow buttons

to change the parameter. When you have
finished, press the enter button to confirm the value.
LED
When the arrow buttons  are used to select the LED option and the enter button is pressed to confirm,
the control unit performs the lamp-test function (all the control unit LEDs flash for several seconds).
LCD
When the arrow buttons  are used to select the LCD option and the enter button is pressed to confirm,
the control unit performs the display test.
Buzzer
When the arrow buttons  are used to select the buzzer option and the enter button is pressed to confirm,
the buzzer will sound intermittently for several seconds.