Notifier SLC Wiring Manual — P/N 51253:U5 12/20/2017 73
Appendix E: Canadian Versions of SLC Devices
UL-listed SLC Device ULC-listed SLC Device Description
Detectors
FSP-951 FSP-951A Analog, addressable intelligent smoke detector that uses a photoelectric
sensing chamber. Listed for use in ducts. Designed to provide open area
protection. FlashScan and CLIP mode. White.
FSP-951-IV FSP-951A-IV Analog, addressable intelligent smoke detector that uses a photoelectric
sensing chamber. Listed for use in ducts. Designed to provide open area
protection. CLIP mode only. Ivory.
FSP-951R FSP-951RA Analog, addressable intelligent photoelectric sensor with remote test
capability. For use with DNR(W) in US; for use with DNRA in Canadian
applications. FlashScan and CLIP mode. White.
FSP-951R-IV FSP-951RA-IV Analog, addressable intelligent photoelectric sensor with remote test
capability. For use with DNR(W) in US; for use with DNRA in Canadian
applications. CLIP mode only. Ivory.
FSP-951T FSP-951TA Adds thermal sensors that will alarm at a fixed temperature of 135°F (57°C).
FlashScan and CLIP mode. White.
FSP-951T-IV FSP-951TA-IV Adds thermal sensors that will alarm at a fixed temperature of 135°F (57°C).
Intelligent Photo/Temperature Detector. CLIP mode only. Ivory.
FST-951 FST-951A High temperature sensor with 190°F (87.8°C) fixed temperature alarm.
FlashScan and CLIP mode. White.
FST-951-IV FST-951A-IV High temperature sensor with 190°F (87.8°C) fixed temperature alarm. CLIP
mode only. Ivory.
FST-951R FST-951RA Incorporates a thermal rate of rise of 15°F (9.4°C). FlashScan and CLIP
mode. White.
FST-951R-IV TC808B3102-
IV
FST-951RA-IV Incorporates a thermal rate of rise of 15°F (9.4°C). CLIP mode only. Ivory.
FST-951H FST-951HA High temperature sensor with 190°F (87.8°C) fixed temperature alarm.
FlashScan and CLIP mode. White.
FST-951H-IV FST-951HA-IV High temperature sensor with 190°F (87.8°C) fixed temperature alarm. CLIP
mode only. Ivory.
FAPT-851 (Acclimate™) FAPT-851A Intelligent detector that combines a photoelectric sensing chamber and fixed
temperature heat detection (135°F/57.2°C). FlashScan capable.
FSB-200, FSB-200S FSB-200A, FSB-200SA Addressable, intelligent, single-ended beam smoke detector with built-in
sensitivity testing. FlashScan and CLIP mode.
FSI-851 FSI-851A Addressable, intelligent smoke detector that incorporates an ionization
sensing chamber. Designed to provide open area protection. FlashScan
capable.
FSP-851 FSP-851A Analog, addressable intelligent smoke detector that uses a photoelectric
sensing chamber. Listed for use in ducts. Designed to provide open area
protection. FlashScan capable.
FSP-851T FSP-851TA Adds thermal sensors that will alarm at a fixed temperature of 135°F (57°C).
FSP-851R FSP-851RA Analog, addressable intelligent photoelectric sensor that is remote test
capable. For use with DNR(W).
FST-851 FST-851A Intelligent thermistor sensing circuit for fast response. Designed to provide
open area protection with 50 foot spacing capability. A fixed temperature
sensor with 135°F fixed temperature alarm. FlashScan capable.
FST-851R FST-851RA Incorporates a thermal rate of rise of 15°F (9.4°C). FlashScan capable.
FST-851H FST-851HA High temperature sensor with 190°F (87.8°C) fixed temperature alarm.
FSD-751PL FSD-751PLA Photoelectric Duct Detector, Low-flow.
FSD-751RPL FSD-751RPLA Photoelectric Duct Detector, Low-flow.
FSH-751 FSH-751A Smoke detector provides early warning smoke detection in hostile
environments where traditional smoke detectors are not practical.
FSL-751 FSL-751A An advanced intelligent photoelectric detector that uses a laser diode,
special optics, and signal processing to obtain extremely high sensitivity.
FSC-851 FSC-851A Intelligent multi-criteria detector that combines photoelectric sensing, heat
detection, carbon monoxide and flame.
FCO-851 FCO-851A Addressable, intelligent detector that combines a photoelectric sensing
chamber combined with Carbon Monoxide (CO) sensors. FlashScan mode
only.

Table of Contents

Other manuals for Honeywell Notifier AFP-100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Notifier AFP-100 and is the answer not in the manual?

Honeywell Notifier AFP-100 Specifications

General IconGeneral
BrandHoneywell
ModelNotifier AFP-100
CategoryControl Panel
LanguageEnglish

Related product manuals