14 NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14
Programming How to Enter Programming
2.2 How to Enter Programming
To enter Program Change, follow these steps:
1. At the “SYSTEM NORMAL” screen, press the
ENTER key. The control panel displays the
“Entry” screen, as shown below:
2. At the “Entry” screen, press the 1 key. The control panel displays the “Enter Password” screen
as shown below:
3. Enter your Program Change password (See “How to Enter a Password” on page 11). The
control panel displays the “Program Change Selection” screen, as shown below:
4. Select a Program Change selection: 1, 2, 3 or 4.
2.3 Basic Program
From the “Program Change Selection” screen, press the 1 key to display the “Basic Program”
screen which provides nine (9) options as shown below:
Press the number of any one of the nine (9) options as detailed below
Option 0=CLR - Clears all existing user programming. For details, refer to How to Clear Memory
(0=
CLR) on page 15. Note: The user is prompted to double-check that this is what is really wanted.
Option 1=AUTO - Add or remove addressable devices to the control panel program. For details,
refer to How to Autoprogram the Control Panel (1=
AUTO) on page page 15.
Option 2=POINT - Modify or delete a point. For details, refer to “How to Modify or Delete a
Point (2=
POINT)” on page page 19.
Option 3=PASSWD - Change the Program Change or the Alter Status password. For details, refer
to “How to Change a Password (3=
PASSWORD)” on page page 25.
Option 4=MESSAGE - Edit the 40-character message that displays on the first line. For details,
refer to “How to Create a System Message (4=
MESSAGE)” on page page 26.
Option 5=ZONES - Edit the 20-character custom zone label for zones 01-99. For details, refer to
“How to Create a Custom Zone Label (5=
ZONE)” on page page 27.
Option 6=SPL FUNCT - Program Releasing Zones and Special Zones. For details, refer to “How
to Program Special Zones (6=
SPL FUNCT)” on page page 27.
Option 7=SYSTEM - Program Global System Functions. For details, refer to “How to Change
Global System Functions (7=
SYSTEM)” on page page 31.
Option 8=CHECK PRG - Check the program for errors. For details, refer to “How to Check the
Program for Errors (8=check prg)” on page 47.
1=PROGRAMMING 2=READ STATUS ENTRY
(ESCAPE TO ABORT)
ENTER PROG OR STAT PASSWORD, THEN ENTER.
(ESCAPE TO ABORT) _
1=BASIC PROGRAM 2=NETWORK
3-UTILITY 4=FLASHSCAN POLL
0=CLR 1=AUTO 2=POINT 3=PASSWD 4=MESSAGE