NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14 95
Appendix C: Intelligent Sensing Applications
C.1 Overview
“Intelligent Sensing” is a set of software algorithms that provide the NF2S-640 with industry-
leading smoke detection capability. You can program Intelligent Sensing functions on a global or
on a per-detector basis.
Intelligent Sensing topics covered in this appendix:
C.2 Features
Intelligent Sensing Applications features include the following:
Drift Compensation and Smoothing
Maintenance Warnings - Three Levels
Self-optimizing Pre-Alarm
Detector Sensitivity
Cooperative Multi-Detector Sensing
C.2.1 Drift Compensation and Smoothing
Drift compensation uses algorithms (U.S. patent pending) that identify and compensate for long-
term changes in the analog readings from each smoke detector. (Typically, dirt and dust
accumulation inside the smoke chamber causes long-term changes in detector readings.) Drift
compensation does the following:
Allows a detector to retain its original ability to detect actual smoke, and resist false alarms,
even as dirt and dust accumulates.
Reduces maintenance requirements by allowing the control panel to automatically perform
the periodic sensitivity measurements required by NFPA Standard.
The software also provides smoothing filters to remove transient noise signals, usually caused by
electrical interference. Different smoothing algorithms are used, depending on the sensitivity
selection of each detector. Refer to “Detector Sensitivity Settings” on page 101 for more
information on detector sensitivity levels.
Topic Page
Intelligent Sensing Applications features – Descriptions of features,
such as Drift Compensation, Sensitivity Adjust, programmable on a per-
detector basis.
page 95
Pre-Alarm – Alert and Action settings, programming (global settings). page 100
Detector Sensitivity Settings – Pre-Alarm and Alarm sensitivity settings
for photo, ion, laser, and multisensor detectors programmable on a per-
detector basis.
page 101
Detector Maintenance Features – Instructions for viewing and printing
detector maintenance information.
page 103

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Notifier NFS2-640/E and is the answer not in the manual?

Honeywell Notifier NFS2-640/E Specifications

General IconGeneral
BrandHoneywell
ModelNotifier NFS2-640/E
CategoryControl Panel
LanguageEnglish

Related product manuals