NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14 51
Setting the Baud Rate of Serial Ports Programming
2.7.2 CRT Serial Port
The default setting for the serial EIA-232 CRT port is “disabled”. To enable the EIA-232 CRT port
at 9600 baud, follow the steps below.
1. From the SYSTEM NORMAL screen, press the
ENTER key to display the Program Entry
screen, as shown below:
2. Press the 1 key. The control panel displays the Enter Password screen, as shown below:
3. Enter CRT96 and press
. The five asterisks that appear when you type in the code
will disappear when you press
.
4. Press
twice to return to the “SYSTEM NORMAL” screen.
5. To switch back to the default network mode (no CRT) repeat steps 1, 2, and 3 entering
NOCRT.
NOTE: The serial EIA-232 CRT port can only be enabled in standalone (non-networked)
applications. The only baud rate supported is 9600.
1=PROGRAMMING 2=READ STATUS ENTRY
(ESCAPE TO ABORT)
ENTER PROG OR STAT PASSWORD, THEN ENTER.
_ (ESCAPE TO ABORT)