NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14 49
FlashScan Poll Programming
To select utility options, follow these steps:
1. Using the arrow keys, move the blinking cursor to a selection.
2. Press the
NEXT or PREVIOUS key to select
- Local Control
- *, 1, 2, 3, 4, 5 (TBL Reminder)
- 0, 1, or 2 (IP ACCESS)
- DCC Mode
3. When finished making selections, press the
ESC key three times to return the control panel to
normal operation.
2.6 FlashScan Poll
From the “Program Change Selection” screen, press the 4 key to access the
“FlashScan Poll” selection screen as shown below:
This menu allows the selection of CLIP (Classic Loop Interface Protocol) or FlashScan detectors
and modules for each loop. Once this screen is accessed, the cursor will be positioned underneath
the Loop #1 Detector selection, blinking the currently selected protocol type. The default selections
are shown in the above figure. This indicates that both Loop #1 and Loop #2 detectors and modules
are selected to use CLIP devices. If FlashScan devices are to be employed, change the blinking
cursor by pressing the Y key or toggle it by using the
PREVIOUS or NEXT key. After the selections
have been made to the detectors and modules of both loops, press the
ENTER key, at which time the
panel will reset.
Most FlashScan devices can be programmed to run in either CLIP or FlashScan mode. Observe one
of the following three options when using FlashScan devices:
Option 1 Program all modules and detectors on an SLC as FlashScan.
(In the “FlashScan Poll” screen, enter Y for DET and Y for MOD. It is possible to
have up to 159 FlashScan modules and 159 FlashScan detectors on this SLC.)
IP ACCESS Note: Use of this option is subject to local AHJ approval.
This option allows the programmer to choose one of three options for Wide Area Network
(WAN) communication. Acceptance of commands, downloads and programming from over the
WAN can be enabled, disabled or timed.
Select IP ACCESS as follows:
Select 0 to disable IP access
Select 1 to enable IP access
Select 2 to enable IP access for two hours.
Note that enabling IP ACCESS allows downloads over a local area network (LAN) or the
internet (Wide Area Network - WAN) using VeriFire Tools through a Noti•Fire•Net(NFN) Web
Server (NWS), or a wide-area enabled NCS through a PC version of NFN Gateway. Always
verify system operation after programming changes are made in this manner.
DCC Mode This option allows the programmer to select whether this panel will participate in DCC (Display
and Control Center) functions. Select Y for participation, N for no participation.
NOTE: For Mass Notification applications, DCC participation should be disabled.
Table 2.35 Utility Program Options (2 of 2)
Utility Option Description
Program Change
Password
FLASHSCAN L1DET L1MOD L2DET L2MOD
N NNN

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Notifier NFS2-640/E and is the answer not in the manual?

Honeywell Notifier NFS2-640/E Specifications

General IconGeneral
BrandHoneywell
ModelNotifier NFS2-640/E
CategoryControl Panel
LanguageEnglish

Related product manuals