NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14 13
Section 2: Programming
2.1 Overview
Program Change is the programming level that lets you change the essential control panel
functions, such as point programming, changing passwords, changing system functions. Included
are four options: Basic Program, Network, FlashScan Poll, and Utility Program.
The structure of the Program Change option is shown below:
Figure 2.1 Program Change Selections
This section contains instructions and sample screens for using the Programming selections:
Basic Program The Basic Program lets you program essential functions, such as clearing
the program, Autoprogramming the system, programming points, and setting system
functions. Refer to “Basic Program” on page 14.
Network Program The Network Program allows programming of network channel
thresholds, network node number, and wiring style.“The Network Program” on page 47.
Utility Program The Utility Program screen provides selections for selecting a Trouble
Reminder per NFPA, a Region setting, and enabling or disabling local control of the
ACKNOWLEDGE/SCROLL DISPLAY, SIGNAL SILENCE, SYSTEM RESET and DRILL keys. Refer to
“The Utility Program” on page 48.
FlashScan Poll The FlashScan Poll screen provides the option for selecting between CLIP
(Classic Loop Interface Poll) and FlashScan Poll. Refer to “FlashScan Poll” on page 49.
Choose one of the Program Change selections: 1, 2, 3 or 4
1 Basic Program options
3 Utility Program options
4 FlashScan Poll options
2 Network Program options
1=BASIC PROGRAM 2=NETWORK
3-UTILITY 4=FLASHSCAN POLL
0=CLR 1=AUTO 2=POINT 3=PASSWD 4=MESSAGE
5=ZONES 6=SPL FUNCT 7=SYSTEM 8=CHECK PRG
THRESHOLD CH.A:H, THRESHOLD CH.B:H
NODE: .000, STYLE7:Y, <ENTER>
REGION=0 TBL.REMIND=2 ALA.SCROLL=N
LOCAL CONTROL=0
FLASHSCAN L1DET L1MOD L2DET L2MOD
NYNY

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Notifier NFS2-640/E and is the answer not in the manual?

Honeywell Notifier NFS2-640/E Specifications

General IconGeneral
BrandHoneywell
ModelNotifier NFS2-640/E
CategoryControl Panel
LanguageEnglish

Related product manuals