NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14 71
How to Program a Releasing Zone Releasing Applications
Figure A.9 Illustrated Example of Cross Zone Programming
A listing of each Cross Zone option and the conditions required to activate the Releasing Zone,
according to the example shown above.
Select a time for the Releasing Zone Delay Timer (refer to“Programming a Delay Timer” on page
61.)
Cross Zone
Selection (Cross=)
Condition(s) Required to Activate the Releasing zone
Cross=N An alarm from any detector or module activates the releasing circuit.
Cross=Y An alarm from any two detectors or modules activates the releasing
circuit.
Cross=Z An alarm from two detectors or modules mapped to different Software
Zones, but mapped to the same Releasing Zone.
An alarm from 2D101 and 2D103
An alarm from 2D102 and 2D104
An alarm from 2D101 and 2D104
An alarm from 2D102 and 2D103
The two detectors listed in each set above are each mapped to different
zones, but both list ZR1 in their CBE.
Cross=H Activation of heat detector 2D104 and one smoke detector (2D101,
21D102, or 2D103) or a module mapped to the same releasing zone.
To Program Do this
Cross Zones Type N, Y, Z, or H in the CROSS= field, or press the
NEXT or PREVIOUS keys,
or , until N, Y, Z or H appears in the that field.
Releasing
Zone ZR1
Software
Zone Z02
Software
Zone Z01
Smoke
Detector
2D102
Heat
Detector
2D104
Smoke
Detector
2D103
Smoke
Detector
2D101
REL
B03
CBE list = Z02 ZR1
CBE list = Z01 ZR1
CBE list = Z01 ZR1
CBE list = ZR1