NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14 75
How to Program a Releasing Zone Releasing Applications
MAN. RELEASE Type Code
The following contains information needed to program a Manual Release switch for a monitor
module
.
Description
A monitor module—connected to a UL-listed manual station (such as the Notifier NBG-12LRA)—
used to manually release agents. A Manual Release switch overrides all timers, such as a Delay
Timer or a Soak Timer. You can install multiple monitor modules with a
MAN. RELEASE Type Code
that work like multiple conventional manual release switches on a conventional zone.
Programming
1. Select a monitor module (refer to “Modify or Delete a Point (2=point)” on page 19) to use for
the manual release function.
2. Select the
MAN. RELEASE Type Code.
3. Select the Releasing Zone (R0-R9) for your releasing application.
4. Press the
ENTER key to save, then press the ESC key until you return to the Program Change
screen.
Example
A programming example of a monitor module programmed as an manual release switch for
Releasing Zone R5.
Figure A.11 Monitor Module Configured as a Manual Release Switch
Releasing Zone selection (R5 shown)
Type Code selection: MAN RELEASE
PROGRM MAN_RELEASE MODULE ADDR 2M101
R5 __ __ __ __ 2M101
SYSTEM
NORMAL
SYSTEM
ACTIVATED
Detector
Control
Module
R05
NBG-12LRA station with Manual Release Lever
B01
Monitor
Module
Type Code
MAN. RELEASE
NBGLRAface.wmf