82 NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14
Releasing Applications How to Program a Releasing Zone
Example
A programming example of a control module programmed as a ULC Release Circuit for Releasing
Zone R5.
Figure A.15 Control Module Configured as a ULC Release Circuit
Type Code
REL CKT ULC
Control
Module
B02
B01
Control
Module
R05
Monitor
Module
Detector
Detec
Detector
Type Code
REL CKT ULC
For example, all control modules programmed with the REL
CKT ULC Type Code activate simultaneously with other
outputs programmed for R5 (B01, B02).