SPYDER MODEL 5 ENGINEERING TOOL USER GUIDE
95 31-00282ES-01
3. Select the template (device) from the drop-down listbox.
4. Confirm the message by clicking OK.
RESULT: The selected template will be used for all devices selected in the Database pane. The Irm Application Type
column in the Database pane indicates that all devices have now the same application type. The master sync group is
formed.
NOTE: Cloning of the device application can be done before or after the source-target definition of the devices and vice
versa.
Applying Master Sync
Allows rolling out the current application (changes) of the source device to all target devices per one step. The
differences in all target device applications are synchronized with the application of the source device.
NOTES: The source-target definition of the devices can be done before or after cloning of the device application and vice
versa.
At least one device must include an application in order establish a master sync group via cloning. If not already done,
clone the application as described in the section “Cloning Application“, p. 94.
The master sync function can be applied in online and offline mode.
Example:
The following procedure shows an offline engineering example with 6 IRM devices created manually using the standard
Niagara New command. The application has been cloned.
Procedure
1. Invoke the Database pane to display the offline devices. In the IRM Application Type column, the same application
type is shown for all devices forming the master sync group.