Indoor temperature limits 59
Cfg_PipeTempCoolThreshold Analog
Value
2071 60 °F 45 to 65 °F Pipe sensor threshold for
cooling
Cfg_PipeTempHighLimit Analog
Value
2072 180 °F 70 to 220 °F Pipe temperature alarm
high limit
Cfg_PipeTempLowLimit Analog
Value
2073 40 °F 30 to 60 °F Pipe temperature alarm
low limit
Cfg_PipeSpaceHeatTempOffset Analog
Value
2074 5 °F 5 to 10 °F 2 pipe single coil hybrid
control space
temperature offset for
heating
Cfg_PipeSpaceCoolTempOffset Analog
Value
2075 -5 °F -10 to -5 °F 2 pipe single coil hybrid
control space
temperature offset for
cooling
Table 24 Indoor temp limits
Name
BACnet
Object
Type
BACnet
Object
Instance
Default
Value
Range Description