54 Control
Control
Equipment
Table 20 Control
Name BACnet Object Type
BACnet
Object
Instance
Default
Value
Range Description
Cfg_Control_MainSensor Multistate Value 9 1 enum{
LocalSensor=1,
RemoteSensor=2,
Multi-Sensor=3}
Temperature/
Humidity
sensor
selection
Cfg_Control_PowerupDelay Analog Value 14 10
seconds
0 to 300 seconds Initial delay to
start control
after power
cycle.
Table 21 Equipment
Name
BACnet
Object
Type
BACnet
Object
Instance
Default
Value
Range Description
Cfg_Mod_StgHt1En Binary
Value
35 0 Disable=0,
Enable=1
Modulating
heat stage
mode
Cfg_Heat_ModHtEnMinOut Analog
Value
96 20 % 0 to 100% Modulating
heat minimum
output when
enabled
Cfg_FanCoilFourPipeSingleCoi
lType
Multistate
Value
87 1 enum{Regulating&Change
Over=1,
6-WayValve=2}
Four pipe
single coil
valve type
Cfg_ChangeoverSwitchPolarity
Type
Multistate
Value
2033 0 enum{Closedwithheat=1,
Closedwithcool=2}
Changeover
switch polarity
type
Cfg_2PipeSingleCoilHeat&Coo
lSysModChangeoverType
Multistate
Value
2034 1 enum{PipeSensor=1,
NetworkInput=2,
ChangeoverSwitch=3}
2 pipe single
coil heat &
cool system
mode
changeover
method
Cfg_Mod_StgCl1En Binary
Value
377 0 Disable=0,
Enable=1
Modulating
cool use stage
1 as enabled
Cfg_Cool_ModClEnMinOut Analog
Value
1461 20 % 0 to 100% Modulating
cool minimum
output when
enabled