66 Wall module configuration
Wall module configuration
Network
Table 32 Wall module configuration
Name
BACnet
Object
Type
BACnet
Object
Instance
Default
Value
Range Description
Cfg_Thermostat_SysSwitch Multistate
Value
8 1 enum{Auto=1,Co
ol=2,
Heat=3,
Ventilation=4,
Off=5}
The system switch
may be used by the
contractor or
occupant to change
the operation of the
unit.
Cfg_Thermostat_BypOverrideTime Analog
Value
10 180
minutes
0 to 1080
minutes
Unoccupied override
time
Cfg_Thermostat_TempOffSpLimit Analog
Value
102 30 °F 0 to 45 °F This point is used to
limit the range of
user adjustable
setpoint.
Cfg_Thermostat_MinCoolSp Analog
Value
12 50 °F 50 to 99 °F Minimum cool
setpoint of
thermostat
Cfg_Thermostat_MaxHeatSp Analog
Value
13 90 °F 40 to 90 °F Maximum heat
setpoint of
thermostat
Cfg_Thermostat_SystemConfig Analog
Value
2023 15 {BIT0=Auto,
BIT1=Heat&Cool
BIT2=Ventilation
BIT3=Off}
To limit available user
configurable options.
BIT 3 Off must be set
as 1.
Cfg_Thermostat_Override Binary
Value
135 0 OverrideOff=0,O
verrideOn=1
Thermostat bypass
override
Cfg_TstatOverrideType Multistate
Value
2035 2 enum{
Permanent=1,Te
mporary=2}
Thermostat override
type
Table 33 Network
Name
BACnet
Object Type
BACnet
Object
Instance
Range Description
no_mstpHeaderCrcError Analog Value 2005 The number of header CRC errors in
received frames
no_mstpDataCrcErr Analog Value 2006 The number of data CRC errors in
received frames
ni_mstpClearErr Binary Value 174 Unclear=0,
Clear=1
Write to 1 and then 0 will clear header
CRC and data CRC count.