Schedule 45
Schedule
Sylk sensor reading
Table 11 Schedule
Name
BACnet
Object
Type
BACnet
Object
Instance
Default
Value
Range Description
no_ScheduleCurrentState Multistate
Value
2027 enum{
Occupied=1,
Unoccupied=2,
Tempporty=3,
Standyby=4}
Current schedule state
no_ScheduleNextState Multistate
Value
2028 enum{
Occupied=1,
Unoccupied=2,
Tempporty=3,
Standyby=4}
Next schedule state
no_ScheduleTimeToNext Analog
Value
2021 1 to 11520
minutes
Time to next schedule state
Table 12 Sylk sensor reading
Name
BACnet
Object
Type
BACnet
Object
Instance
Range Description
no_SylkAddr2Temp Analog
Value
223 -40 to 150 °F TR40-H-CO2: Temperature
(May also use models TR40, TR40-H, TR40-CO2,
TR40-H-CO2)
no_SylkAddr2Hum Analog
Value
224 0 to 100% RH TR40-H-CO2: Humidity
(May also use models TR40, TR40-H, TR40-CO2,
TR40-H-CO2)
no_SylkAddr2CO2 Analog
Value
225 0 to 2000 ppm TR40-H-CO2: CO2.
(May also use models TR40-CO2, TR40-H-CO2)
no_SylkAddr3Temp Analog
Value
226 -40 to 150 °F Address 3 TR40: Temperature
no_SylkAddr4Temp Analog
Value
227 -40 to 150 °F Address 4 TR40: Temperature
no_SylkAddr5Temp Analog
Value
228 -40 to 150 °F Address 5 TR40: Temperature
no_SylkAddr10Temp Analog
Value
235 -40 to 200 °F Address 10 C7400S: Temperature
no_SylkAddr10Hum Analog
Value
236 0 to 100% RH Address 10 C7400S: Humidity