58 General
General
Home
Indoor temperature limits
Table 22 General
Name
BACnet
Object
Type
BACnet
Object
Instance
Default
Value
Range Description
Cfg_Thermostat_TstUnitSel Binary
Value
136 0 Fahrenheit=0,
Celsius=1
Thermostat unit definition
(Imperial/ Metric)
Cfg_BrandType Multistat
e Value
505 1 enum{Honeywell=1
Alerton=2,
None=3}
Vendor ID and Vendor
name will be changed
when modify brand type.
Table 23 Home
Name
BACnet
Object
Type
BACnet
Object
Instance
Default
Value
Range Description
Cfg_StdbyConfig Binary
Value
2034 0 StandbyAsUnoccupied
=0,
StandbyAsOccupied=1
Standby action
Cfg_Thermostat_ClAdjStPt Analog
Value
256 -45 to 45 °F Temporary cool
setpoint adjustment
from User or from the
supervisor.
Cfg_Thermostat_HtAdjStPt Analog
Value
257 -45 to 45 °F Temporary heat
setpoint adjustment
from user or from the
supervisor.
Table 24 Indoor temp limits
Name
BACnet
Object
Type
BACnet
Object
Instance
Default
Value
Range Description
Cfg_SpcAlarm_TempHighLim Analog
Value
254 90 °F 90 to 150 °F Space temperature alarm
high limit
Cfg_SpcAlarm_TempLowLim Analog
Value
255 45 °F 0 to 60 °F Space temperature alarm
low limit
Cfg_DaTAlarm_TempHighLim Analog
Value
332 140 °F 70 to 180 °F Discharge air temperature
alarm high limit
Cfg_DATAlarmTempLowLim Analog
Value
333 45 °F 35 to 65 °F Discharge air temperature
alarm low limit
Cfg_PipeTempHeatThreshold Analog
Value
2070 80 °F 70 to 90 °F Pipe sensor threshold for
heating