72 Network sensor configuration
Network sensor configuration
Service mode
Table 35 Network sensor configuration
Name
BACnet
Object
Type
BACnet
Object
Instance
Default
Value
Range Description
Cfg_NetOccSenFailDetEn Binary
Value
159 1 Disable=0,
Enable=1
Occupancy sensor
fail detect enable
Cfg_NetOccSenFailFalbck Analog
Value
262 2 InvalidValue(Null)=0,
LastKnownGoodValue=1,
FixedValue=2
Occupancy sensor
fail detect fallback
Cfg_NetOccSenFailFxdVal Multistate
Value
2021 5 enum{Occupied=1,
Unoccupied=2,
Bypass=3,
Standby=4,
NoOverride=5}
Occupancy sensor
fail detect fallback
value
Cfg_NetOccSenFailDetDly Analog
Value
263 300
seconds
0 to 3600 seconds Occupancy sensor
fail detect delay
Cfg_NetShtdwnFailDetEn Binary
Value
164 1 Disable=0,
Enable=1
Shut down fail detect
enable
Cfg_NetShtdwnFailFalbck Analog
Value
273 2 InvalidValue(Null)=0,
LastKnownGoodValue=1,
FixedValue=2
Shut down fail detect
fallback
Cfg_NetShtdwnFailFxdVal Binary
Value
165 0 Normal=0,
Shutdown=1
Shut down fail detect
fallback value
Cfg_NetShtdwnFailDetDly Analog
Value
274 300
seconds
0 to 3600 seconds Shut down fail detect
delay
Table 36 Service mode
Name
BACnet
Object
Type
BACnet
Object
Instance
Default
Value
Range Description
ni_ServiceModeEn Binary
Value
6 0 NoOverride=0,
Service=1
Service mode network
input to felicitate installer
during commissioning/
maintenance to shut
down all equipment.
ni_ServiceFan Multistate
Value
2026 1 enum{
0ff=1,
On=2,
Low=3,
Medium=4,
High=5}
Fan speed configuration
network input for single/
two/three speed fan when
service mode is enabled.