Recovery setpoint configuration 63
Recovery setpoint configuration
Cfg_CoolTimeOut Analog
Value
2101 4 hours 1 to 4 hours When heating/cooling keep
working for timeout time check
whether pipe temperature meet
pipe sensor threshold.
Table 28 Recovery setpoint configuration
Name
BACnet
Object
Type
BACnet
Object
Instance
Default
Value
Range Description
Cfg_Recovery_MaxCoolRampRate Analog Value 18 6 °F/hr 0 to 20 °F/hr Maximum cooling
setpoint ramp
Cfg_Recovery_MaxHeatRampRate Analog Value 22 8 °F/hr 0 to 36 °F/hr Maximum cooling
setpoint ramp
Table 27 Purge (Continued)
Name
BACnet
Object
Type
BACnet
Object
Instance
Default
Value
Range Description