60 Multi sensor
Multi sensor
Table 25 Multi sensor
Name
BACnet
Object
Type
BACnet
Object
Instance
Default
Value
Range Description
Cfg_ZoneMultiSens_Control Multistate
Value
130 1 enum{
Average=1
Min=2,
Max=3,
Smart=4}
Main control sensor
configuration
Cfg_ZoneMultiSens_Sens1_Wt Analog
Value
33
10 0 to 10
A weighted average
allows individual sensors
to have more influence
on the average
calculation. Sensor 1 is
the local onboard
temperature sensor.
Cfg_ZoneMultiSens_Sens2_Wt Analog
Value
34
10 0 to 10
A weighted average
allows individual sensors
to have more influence
on the average
calculation. Sensor 2 is
the remote TR40 Sylk
temperature sensor with
Addr 2.
Cfg_ZoneMultiSens_Sens3_Wt Analog
Value
35
10 0 to 10
A weighted average
allows individual sensors
to have more influence
on the average
calculation. Sensor 3 is
the remote TR40 Sylk
temperature sensor with
Addr 3.
Cfg_ZoneMultiSens_Sens4_Wt Analog
Value
36
10 0 to 10
A weighted average
allows individual sensors
to have more influence
on the average
calculation. Sensor 4 is
the remote TR40 Sylk
temperature sensor with
Addr 4.
Cfg_ZoneMultiSens_Sens5_Wt Analog
Value
37
10 0 to 10
A weighted average
allows individual sensors
to have more influence
on the average
calculation. Sensor 5 is
the remote TR40 Sylk
temperature sensor with
Addr 5.