Sylk sensor configuration 65
Sylk sensor configuration
Cfg_SylkCalOffset_Sylk
Bus5Temp
Analog
Value
28 0 °F -10 to 10 °F TR40_5 Temperature
calibration offset
Cfg_SylkCalOffset_Sylk
Bus10Temp
Analog
Value
31 0 °F -10 to 10 °F C7400S Discharge Air
Temperature calibration
offset
Cfg_SylkCalOffset_Sylk
Bus10RH
Analog
Value
32 0 %RH -10 to 10%RH C7400S Discharge Air
Humidity calibration offset
Table 31 Sylk sensor configuration
Name
BACnet
Object
Type
BACnet
Object
Instance
Default
Value
Range Description
Cfg_Sylk_SylkBus2Type Multistate
Value
2032 1 enum{
TR40=1,
TR50=2}
Sylk bus addr-2 device type
Cfg_Sylk_SylkBus2En Multistate
Value
85 1 enum{
NotConfigured=1,
TempOnly=2,
TempHum=3,
TempHumCO2=4,
TempCO2=5}
Sylk bus addr-2 device
enable/ disable
Cfg_Sylk_SylkBus3En Binary
Value
147 0 Disable=0,
Enable=1
Sylk bus addr-3 device
enable/ disable
Cfg_Sylk_SylkBus4En Binary
Value
148 0 Disable=0,
Enable=1
Sylk bus addr-4 device
enable/ disable
Cfg_Sylk_SylkBus5En Binary
Value
149 0 Disable=0,
Enable=1
Sylk bus addr-5 device
enable/ disable
Cfg_Sylk_SylkBus10En Binary
Value
153 0 Disable=0,
Enable=1
Sylk bus addr-10 device
enable/ disable
Table 30 Sylk calibration offsets (Continued)
Name
BACnet
Object
Type
BACnet
Object
Instance
Default
Value
Range Description