62 Occupancy setpoints
Occupancy setpoints
Purge
Table 26 Occupancy setpoints
Name
BACnet
Object Type
BACnet
Object
Instance
Default
Value
Range Description
Cfg_Setpoints_OccHeatSp Analog Value 7 68 °F 40 to 99 °F Occupied
heating
setpoint
Cfg_Setpoints_OccCoolSp Analog Value 4 76 °F 40 to 99 °F Occupied
cooling
setpoint
Cfg_Setpoints_StbyHeatSp Analog Value 8 65 °F 40 to 99 °F Standby
heating
setpoint
Cfg_Setpoints_StbyCoolSp Analog Value 5 80 °F 40 to 99 °F Standby
cooling
setpoint
Cfg_Setpoints_UnOccHeatSp Analog Value 9 55 °F 40 to 99 °F Unoccupied
heating
setpoint
Cfg_Setpoints_UnOccCoolSp Analog Value 6 85 °F 40 to 99 °F Unoccupied
cooling
setpoint
Table 27 Purge
Name
BACnet
Object
Type
BACnet
Object
Instance
Default
Value
Range Description
Cfg_PipePurgeTime Analog
Value
2025 5
minutes
0 to 5 minutes Pipe purge duration
Cfg_PipePurgeInterval Analog
Value
2079 0.5 hours 0.5 to 2 hours Pipe purge interval
Cfg_ValveCycle Multistate
Value
2025 1 enum{
1min/24hours=1,
2min/24hours=2,
Disable=3}
Valve cycle type
Cfg_TimeOut Analog
Value
2080 4 hours 1 to 4 hours When heating keeps working for
timeout time check whether pipe
temperature meet pipe sensor
threshold.
Cfg_HybridControlEna
bleHeat
Binary
Value
2053 1 Off=0,
On=1
2 pipe single coil heat hybrid
control enable flag
Cfg_HybridControLEn
ableCool
Binary
Value
2054 1 Off=0,
On=1
2 pipe single coil cool hybrid
control enable flag