Equipment 55
Cfg_FanCoilType Multistate
Value
575 1 enum{4PipeDualCoil=1,
4PipesingleCoil=2,
PipeSingleCoil=3}
Fan coil type
Cfg_FanCoilHtgType Multistate
Value
576 2 enum{None=1,
OnOff=2,
Floating=3,
Modulating=4}
4 pipe dual coil
heating valve
type, 4 pipe
single coil/
2 pipe single
coil valve type
Cfg_FanCoilClgType Multistate
Value
577 2 enum{None=1,
OnOff=2,
Floating=3,
Modulating=4}
4 pipe dual coil
cooling valve
type
Cfg_FanCoilHtgDriveTime Analog
Value
1721 90
seconds
0 to 240 seconds 4 pipe dual coil
floating
heating drive
time, 4 pipe
single coil/2
pipe single coil
valve drive
time
Cfg_FanCoilClgDriveTime Analog
Value
1722 90
seconds
0 to 240 seconds 4 pipe dual coil
floating
cooling drive
time
Cfg_FanCoilTwoPipeSingleCoil
Type
Multistate
Value
580 1 enum{Heat&Cool=1,
HeatingOnly=2,
CoolingOnly=3}
2 pipe single
coil type
Cfg_FanCoilHtgDriveType Multistate
Value
578 1 enum{Direct=1,
Reverse=2}
4 pipe dual coil
floating
heating drive
type, 4 pipe
single coil/2
pipe single coil
floating valve
drive type
Cfg_FanCoilClgDriveType Multistate
Value
579 1 enum{Direct=1,
Reverse=2}
4 pipe dual coil
floating
cooling drive
time
Cfg_FanCoilHtgFloatingSyncE
n
Binary
Value
453 1 Disable=0,
Enable=1
4 pipe dual coil
floating
heating sync
enable, 4 pipe
single coil/2
pipe single coil
floating valve
sync enable
Table 21 Equipment (Continued)
Name
BACnet
Object
Type
BACnet
Object
Instance
Default
Value
Range Description