56 Equipment
Cfg_FanCoilClgFloatingSyncE
n
Binary
Value
462 1 Disable=0,
Enable=1
4 pipe dual coil
floating
cooling sync
enable
Cfg_FanCoilOnOffClgVlvChar Binary
Value
459 0 NormallyClosed=0,
NormallyOpen=1
4 pipe dual coil
on/off cooling
valve
characteristic
Cfg_FanCoilonOffHtgVlvChar Binary
Value
458 0 NormallyClosed=0,
NormallyOpen=1
4 pipe dual coil
on/off heating
valve
characteristic,
4 pipe single
coil/2 pipe
single coil on/
off valve
characteristic
Cfg_Cool_valvefloatEnMinOut Analog
Value
2007 5% 0 to 100% 4 pipe dual coil
floating
Cooling valve
minimum
output when
enabled
Cfg_Heat_valvefloatEnMinOut Analog
Value
2008 5% 0 to 100% 4 pipe dual coil
floating
heating valve
minimum
output when
enabled, 4
pipe single
coil/2 pipe
single coil
floating valve
minimum
output when
enabled
Cfg_ChangeOverValveType Binary
Value
2036 0 EnergizeOnHeat=0,
EnergizeOnCool=1
4 pipe single
coil
changeover
valve type
Cfg_SixwayValveOutput Binary
Value
2037 1 0-10V=0,
2-10V=1
6-way valve
type
Cfg_SixwayValveDriveType Binary
Value
2038 0 Direct=0,
Reverse=1
Six way valve
direct/reverse
enable flag
Cfg_SixwayValveHeatingMinO
utput
Analog
Value
2066 2 V 0 to 10 V 6-way valve
heat min
output
Table 21 Equipment (Continued)
Name
BACnet
Object
Type
BACnet
Object
Instance
Default
Value
Range Description