APPENDIX A: HARDWARE SETUP XI581/2 BUSWIDE OPERATOR INTERFACE
EN2B-0126 (74-3554-8) 100
When the backlighting jumper is enabled, the first key stroke from any of the
eight operating keys activates the backlighting feature. If no key entry occurs for
more than 10 minutes, the backlighting automatically turns itself off until the next
keystroke occurs.
3. For XI581AH units, continue with Step 6.
For XI582AH units, route wire end of XW564/XW565/XW582/XW583 Cable
through round opening (back to front) in XI582AH back cover, and fix cable with
the strain relief.
C
6
9
74
a
4. Attach wires to terminal block on inside of XI582AH back cover according to the
following figure.
WHITE
GREEN
BROWN
YELLOW
GREY
1234
C
6
9
7
5
a
NOTE: Grey wire is not used.
5. Replace the connector removed in Step 3.
6. Snap XI582AH back cover in place.
RESULT: The XI582AH can now be moved to the desired Excel controller and
connected to it. See section "GETTING STARTED" (page 3) for
details.