XI581/2 BUSWIDE OPERATOR INTERFACE EVERYDAY OPERATIONS
41 EN2B-0126 (74-3554-8)
is invalid. An alarm “Invalid User ID” will be issued (valid for CARE
3.00.00 onwards).
Data Point Wiring Check
Purpose To check out or troubleshoot the system by manually setting outputs and verifying
inputs.
Steps 1 and 2 of the Start-up Sequence bring up the following screen:
01.01.1999 Controller: 23
14:45 Modem Part: inactive
Applic. Mem. Size: 128 KB
Controller Setup
Application Selection
Data Point Wiring Check
3. Use the arrow keys to move to and highlight Data Point Wiring Check and
press Enter () to complete the selection.
RESULT: The first 'Data Point Wiring Check' screen appears.
Data Point Wiring Check
Default Data Points
DIO Module Assignment
NOTE: The DIO Module Assignment option appears only if there is a
LonMark™ interface available.
Default Data Points
Purpose To set up the test mode with default user addresses for each of the physical inputs
and outputs.
Select Default Data Points 4. From the 'Data Point Wiring Check' screen shown above, select Default Data
Points and press Enter () to complete the selection.
RESULT: The following screen appears with additional options.
Default Data Points
Display Data Points
Alarm History
BACK
Alarm History Displays current alarms.
Display
Data Points Displays data points according to point type.
5. Use the arrow keys to move to and highlight Display Data Points and press
Enter () to complete the selection.
RESULT: The display window lists the default data points.